Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers
Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory cond...
Ausführliche Beschreibung
Autor*in: |
Stanisław Czapp [verfasserIn] Daniel Kowalak [verfasserIn] Kornel Borowski [verfasserIn] |
---|
Format: |
E-Artikel |
---|---|
Sprache: |
Englisch ; Polnisch |
Erschienen: |
2014 |
---|
Schlagwörter: |
---|
Übergeordnetes Werk: |
In: Acta Energetica - ENERGA SA, 2016, 21(2014), 4, Seite 67-73 |
---|---|
Übergeordnetes Werk: |
volume:21 ; year:2014 ; number:4 ; pages:67-73 |
Links: |
---|
DOI / URN: |
10.12736/issn.2300-3022.2014406 |
---|
Katalog-ID: |
DOAJ002907399 |
---|
LEADER | 01000caa a22002652 4500 | ||
---|---|---|---|
001 | DOAJ002907399 | ||
003 | DE-627 | ||
005 | 20230309172438.0 | ||
007 | cr uuu---uuuuu | ||
008 | 230225s2014 xx |||||o 00| ||eng c | ||
024 | 7 | |a 10.12736/issn.2300-3022.2014406 |2 doi | |
035 | |a (DE-627)DOAJ002907399 | ||
035 | |a (DE-599)DOAJba8e03432d4b469b866ab70d1f99c4a4 | ||
040 | |a DE-627 |b ger |c DE-627 |e rakwb | ||
041 | |a eng |a pol | ||
050 | 0 | |a HD9502-9502.5 | |
100 | 0 | |a Stanisław Czapp |e verfasserin |4 aut | |
245 | 1 | 0 | |a Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers |
264 | 1 | |c 2014 | |
336 | |a Text |b txt |2 rdacontent | ||
337 | |a Computermedien |b c |2 rdamedia | ||
338 | |a Online-Ressource |b cr |2 rdacarrier | ||
520 | |a Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed. | ||
650 | 4 | |a residual current devices | |
650 | 4 | |a short-circuit currents | |
650 | 4 | |a back-up protection | |
653 | 0 | |a Energy industries. Energy policy. Fuel trade | |
700 | 0 | |a Daniel Kowalak |e verfasserin |4 aut | |
700 | 0 | |a Kornel Borowski |e verfasserin |4 aut | |
773 | 0 | 8 | |i In |t Acta Energetica |d ENERGA SA, 2016 |g 21(2014), 4, Seite 67-73 |w (DE-627)1023271311 |x 23003022 |7 nnns |
773 | 1 | 8 | |g volume:21 |g year:2014 |g number:4 |g pages:67-73 |
856 | 4 | 0 | |u https://doi.org/10.12736/issn.2300-3022.2014406 |z kostenfrei |
856 | 4 | 0 | |u https://doaj.org/article/ba8e03432d4b469b866ab70d1f99c4a4 |z kostenfrei |
856 | 4 | 0 | |u http://actaenergetica.org/en/articles/acta-energetica-042014/thermal-and-electrodynamic-risk-of-residual-current-devices-in-the-case-of-back-up-protection-by-overcurrent-circuit-breakers/ |z kostenfrei |
856 | 4 | 2 | |u https://doaj.org/toc/2300-3022 |y Journal toc |z kostenfrei |
912 | |a GBV_USEFLAG_A | ||
912 | |a SYSFLAG_A | ||
912 | |a GBV_DOAJ | ||
912 | |a GBV_ILN_20 | ||
912 | |a GBV_ILN_22 | ||
912 | |a GBV_ILN_23 | ||
912 | |a GBV_ILN_24 | ||
912 | |a GBV_ILN_31 | ||
912 | |a GBV_ILN_39 | ||
912 | |a GBV_ILN_40 | ||
912 | |a GBV_ILN_60 | ||
912 | |a GBV_ILN_62 | ||
912 | |a GBV_ILN_63 | ||
912 | |a GBV_ILN_65 | ||
912 | |a GBV_ILN_69 | ||
912 | |a GBV_ILN_70 | ||
912 | |a GBV_ILN_73 | ||
912 | |a GBV_ILN_95 | ||
912 | |a GBV_ILN_105 | ||
912 | |a GBV_ILN_110 | ||
912 | |a GBV_ILN_151 | ||
912 | |a GBV_ILN_161 | ||
912 | |a GBV_ILN_170 | ||
912 | |a GBV_ILN_213 | ||
912 | |a GBV_ILN_230 | ||
912 | |a GBV_ILN_285 | ||
912 | |a GBV_ILN_293 | ||
912 | |a GBV_ILN_602 | ||
912 | |a GBV_ILN_2014 | ||
912 | |a GBV_ILN_4012 | ||
912 | |a GBV_ILN_4037 | ||
912 | |a GBV_ILN_4112 | ||
912 | |a GBV_ILN_4125 | ||
912 | |a GBV_ILN_4126 | ||
912 | |a GBV_ILN_4249 | ||
912 | |a GBV_ILN_4305 | ||
912 | |a GBV_ILN_4306 | ||
912 | |a GBV_ILN_4307 | ||
912 | |a GBV_ILN_4313 | ||
912 | |a GBV_ILN_4322 | ||
912 | |a GBV_ILN_4323 | ||
912 | |a GBV_ILN_4324 | ||
912 | |a GBV_ILN_4325 | ||
912 | |a GBV_ILN_4335 | ||
912 | |a GBV_ILN_4338 | ||
912 | |a GBV_ILN_4367 | ||
912 | |a GBV_ILN_4700 | ||
951 | |a AR | ||
952 | |d 21 |j 2014 |e 4 |h 67-73 |
author_variant |
s c sc d k dk k b kb |
---|---|
matchkey_str |
article:23003022:2014----::hraadlcrdnmcikfeiulurndvcsnhcsobcupoeto |
hierarchy_sort_str |
2014 |
callnumber-subject-code |
HD |
publishDate |
2014 |
allfields |
10.12736/issn.2300-3022.2014406 doi (DE-627)DOAJ002907399 (DE-599)DOAJba8e03432d4b469b866ab70d1f99c4a4 DE-627 ger DE-627 rakwb eng pol HD9502-9502.5 Stanisław Czapp verfasserin aut Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers 2014 Text txt rdacontent Computermedien c rdamedia Online-Ressource cr rdacarrier Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed. residual current devices short-circuit currents back-up protection Energy industries. Energy policy. Fuel trade Daniel Kowalak verfasserin aut Kornel Borowski verfasserin aut In Acta Energetica ENERGA SA, 2016 21(2014), 4, Seite 67-73 (DE-627)1023271311 23003022 nnns volume:21 year:2014 number:4 pages:67-73 https://doi.org/10.12736/issn.2300-3022.2014406 kostenfrei https://doaj.org/article/ba8e03432d4b469b866ab70d1f99c4a4 kostenfrei http://actaenergetica.org/en/articles/acta-energetica-042014/thermal-and-electrodynamic-risk-of-residual-current-devices-in-the-case-of-back-up-protection-by-overcurrent-circuit-breakers/ kostenfrei https://doaj.org/toc/2300-3022 Journal toc kostenfrei GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_213 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_602 GBV_ILN_2014 GBV_ILN_4012 GBV_ILN_4037 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4249 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4335 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 AR 21 2014 4 67-73 |
spelling |
10.12736/issn.2300-3022.2014406 doi (DE-627)DOAJ002907399 (DE-599)DOAJba8e03432d4b469b866ab70d1f99c4a4 DE-627 ger DE-627 rakwb eng pol HD9502-9502.5 Stanisław Czapp verfasserin aut Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers 2014 Text txt rdacontent Computermedien c rdamedia Online-Ressource cr rdacarrier Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed. residual current devices short-circuit currents back-up protection Energy industries. Energy policy. Fuel trade Daniel Kowalak verfasserin aut Kornel Borowski verfasserin aut In Acta Energetica ENERGA SA, 2016 21(2014), 4, Seite 67-73 (DE-627)1023271311 23003022 nnns volume:21 year:2014 number:4 pages:67-73 https://doi.org/10.12736/issn.2300-3022.2014406 kostenfrei https://doaj.org/article/ba8e03432d4b469b866ab70d1f99c4a4 kostenfrei http://actaenergetica.org/en/articles/acta-energetica-042014/thermal-and-electrodynamic-risk-of-residual-current-devices-in-the-case-of-back-up-protection-by-overcurrent-circuit-breakers/ kostenfrei https://doaj.org/toc/2300-3022 Journal toc kostenfrei GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_213 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_602 GBV_ILN_2014 GBV_ILN_4012 GBV_ILN_4037 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4249 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4335 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 AR 21 2014 4 67-73 |
allfields_unstemmed |
10.12736/issn.2300-3022.2014406 doi (DE-627)DOAJ002907399 (DE-599)DOAJba8e03432d4b469b866ab70d1f99c4a4 DE-627 ger DE-627 rakwb eng pol HD9502-9502.5 Stanisław Czapp verfasserin aut Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers 2014 Text txt rdacontent Computermedien c rdamedia Online-Ressource cr rdacarrier Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed. residual current devices short-circuit currents back-up protection Energy industries. Energy policy. Fuel trade Daniel Kowalak verfasserin aut Kornel Borowski verfasserin aut In Acta Energetica ENERGA SA, 2016 21(2014), 4, Seite 67-73 (DE-627)1023271311 23003022 nnns volume:21 year:2014 number:4 pages:67-73 https://doi.org/10.12736/issn.2300-3022.2014406 kostenfrei https://doaj.org/article/ba8e03432d4b469b866ab70d1f99c4a4 kostenfrei http://actaenergetica.org/en/articles/acta-energetica-042014/thermal-and-electrodynamic-risk-of-residual-current-devices-in-the-case-of-back-up-protection-by-overcurrent-circuit-breakers/ kostenfrei https://doaj.org/toc/2300-3022 Journal toc kostenfrei GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_213 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_602 GBV_ILN_2014 GBV_ILN_4012 GBV_ILN_4037 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4249 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4335 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 AR 21 2014 4 67-73 |
allfieldsGer |
10.12736/issn.2300-3022.2014406 doi (DE-627)DOAJ002907399 (DE-599)DOAJba8e03432d4b469b866ab70d1f99c4a4 DE-627 ger DE-627 rakwb eng pol HD9502-9502.5 Stanisław Czapp verfasserin aut Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers 2014 Text txt rdacontent Computermedien c rdamedia Online-Ressource cr rdacarrier Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed. residual current devices short-circuit currents back-up protection Energy industries. Energy policy. Fuel trade Daniel Kowalak verfasserin aut Kornel Borowski verfasserin aut In Acta Energetica ENERGA SA, 2016 21(2014), 4, Seite 67-73 (DE-627)1023271311 23003022 nnns volume:21 year:2014 number:4 pages:67-73 https://doi.org/10.12736/issn.2300-3022.2014406 kostenfrei https://doaj.org/article/ba8e03432d4b469b866ab70d1f99c4a4 kostenfrei http://actaenergetica.org/en/articles/acta-energetica-042014/thermal-and-electrodynamic-risk-of-residual-current-devices-in-the-case-of-back-up-protection-by-overcurrent-circuit-breakers/ kostenfrei https://doaj.org/toc/2300-3022 Journal toc kostenfrei GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_213 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_602 GBV_ILN_2014 GBV_ILN_4012 GBV_ILN_4037 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4249 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4335 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 AR 21 2014 4 67-73 |
allfieldsSound |
10.12736/issn.2300-3022.2014406 doi (DE-627)DOAJ002907399 (DE-599)DOAJba8e03432d4b469b866ab70d1f99c4a4 DE-627 ger DE-627 rakwb eng pol HD9502-9502.5 Stanisław Czapp verfasserin aut Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers 2014 Text txt rdacontent Computermedien c rdamedia Online-Ressource cr rdacarrier Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed. residual current devices short-circuit currents back-up protection Energy industries. Energy policy. Fuel trade Daniel Kowalak verfasserin aut Kornel Borowski verfasserin aut In Acta Energetica ENERGA SA, 2016 21(2014), 4, Seite 67-73 (DE-627)1023271311 23003022 nnns volume:21 year:2014 number:4 pages:67-73 https://doi.org/10.12736/issn.2300-3022.2014406 kostenfrei https://doaj.org/article/ba8e03432d4b469b866ab70d1f99c4a4 kostenfrei http://actaenergetica.org/en/articles/acta-energetica-042014/thermal-and-electrodynamic-risk-of-residual-current-devices-in-the-case-of-back-up-protection-by-overcurrent-circuit-breakers/ kostenfrei https://doaj.org/toc/2300-3022 Journal toc kostenfrei GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_213 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_602 GBV_ILN_2014 GBV_ILN_4012 GBV_ILN_4037 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4249 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4335 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 AR 21 2014 4 67-73 |
language |
English Polish |
source |
In Acta Energetica 21(2014), 4, Seite 67-73 volume:21 year:2014 number:4 pages:67-73 |
sourceStr |
In Acta Energetica 21(2014), 4, Seite 67-73 volume:21 year:2014 number:4 pages:67-73 |
format_phy_str_mv |
Article |
institution |
findex.gbv.de |
topic_facet |
residual current devices short-circuit currents back-up protection Energy industries. Energy policy. Fuel trade |
isfreeaccess_bool |
true |
container_title |
Acta Energetica |
authorswithroles_txt_mv |
Stanisław Czapp @@aut@@ Daniel Kowalak @@aut@@ Kornel Borowski @@aut@@ |
publishDateDaySort_date |
2014-01-01T00:00:00Z |
hierarchy_top_id |
1023271311 |
id |
DOAJ002907399 |
language_de |
englisch polnisch |
fullrecord |
<?xml version="1.0" encoding="UTF-8"?><collection xmlns="http://www.loc.gov/MARC21/slim"><record><leader>01000caa a22002652 4500</leader><controlfield tag="001">DOAJ002907399</controlfield><controlfield tag="003">DE-627</controlfield><controlfield tag="005">20230309172438.0</controlfield><controlfield tag="007">cr uuu---uuuuu</controlfield><controlfield tag="008">230225s2014 xx |||||o 00| ||eng c</controlfield><datafield tag="024" ind1="7" ind2=" "><subfield code="a">10.12736/issn.2300-3022.2014406</subfield><subfield code="2">doi</subfield></datafield><datafield tag="035" ind1=" " ind2=" "><subfield code="a">(DE-627)DOAJ002907399</subfield></datafield><datafield tag="035" ind1=" " ind2=" "><subfield code="a">(DE-599)DOAJba8e03432d4b469b866ab70d1f99c4a4</subfield></datafield><datafield tag="040" ind1=" " ind2=" "><subfield code="a">DE-627</subfield><subfield code="b">ger</subfield><subfield code="c">DE-627</subfield><subfield code="e">rakwb</subfield></datafield><datafield tag="041" ind1=" " ind2=" "><subfield code="a">eng</subfield><subfield code="a">pol</subfield></datafield><datafield tag="050" ind1=" " ind2="0"><subfield code="a">HD9502-9502.5</subfield></datafield><datafield tag="100" ind1="0" ind2=" "><subfield code="a">Stanisław Czapp</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="245" ind1="1" ind2="0"><subfield code="a">Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers</subfield></datafield><datafield tag="264" ind1=" " ind2="1"><subfield code="c">2014</subfield></datafield><datafield tag="336" ind1=" " ind2=" "><subfield code="a">Text</subfield><subfield code="b">txt</subfield><subfield code="2">rdacontent</subfield></datafield><datafield tag="337" ind1=" " ind2=" "><subfield code="a">Computermedien</subfield><subfield code="b">c</subfield><subfield code="2">rdamedia</subfield></datafield><datafield tag="338" ind1=" " ind2=" "><subfield code="a">Online-Ressource</subfield><subfield code="b">cr</subfield><subfield code="2">rdacarrier</subfield></datafield><datafield tag="520" ind1=" " ind2=" "><subfield code="a">Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed.</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">residual current devices</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">short-circuit currents</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">back-up protection</subfield></datafield><datafield tag="653" ind1=" " ind2="0"><subfield code="a">Energy industries. Energy policy. Fuel trade</subfield></datafield><datafield tag="700" ind1="0" ind2=" "><subfield code="a">Daniel Kowalak</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="700" ind1="0" ind2=" "><subfield code="a">Kornel Borowski</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="773" ind1="0" ind2="8"><subfield code="i">In</subfield><subfield code="t">Acta Energetica</subfield><subfield code="d">ENERGA SA, 2016</subfield><subfield code="g">21(2014), 4, Seite 67-73</subfield><subfield code="w">(DE-627)1023271311</subfield><subfield code="x">23003022</subfield><subfield code="7">nnns</subfield></datafield><datafield tag="773" ind1="1" ind2="8"><subfield code="g">volume:21</subfield><subfield code="g">year:2014</subfield><subfield code="g">number:4</subfield><subfield code="g">pages:67-73</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">https://doi.org/10.12736/issn.2300-3022.2014406</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">https://doaj.org/article/ba8e03432d4b469b866ab70d1f99c4a4</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">http://actaenergetica.org/en/articles/acta-energetica-042014/thermal-and-electrodynamic-risk-of-residual-current-devices-in-the-case-of-back-up-protection-by-overcurrent-circuit-breakers/</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="2"><subfield code="u">https://doaj.org/toc/2300-3022</subfield><subfield code="y">Journal toc</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_USEFLAG_A</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">SYSFLAG_A</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_DOAJ</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_20</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_22</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_23</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_24</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_31</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_39</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_40</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_60</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_62</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_63</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_65</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_69</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_70</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_73</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_95</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_105</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_110</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_151</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_161</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_170</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_213</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_230</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_285</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_293</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_602</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2014</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4012</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4037</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4112</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4125</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4126</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4249</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4305</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4306</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4307</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4313</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4322</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4323</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4324</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4325</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4335</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4338</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4367</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4700</subfield></datafield><datafield tag="951" ind1=" " ind2=" "><subfield code="a">AR</subfield></datafield><datafield tag="952" ind1=" " ind2=" "><subfield code="d">21</subfield><subfield code="j">2014</subfield><subfield code="e">4</subfield><subfield code="h">67-73</subfield></datafield></record></collection>
|
callnumber-first |
H - Social Science |
author |
Stanisław Czapp |
spellingShingle |
Stanisław Czapp misc HD9502-9502.5 misc residual current devices misc short-circuit currents misc back-up protection misc Energy industries. Energy policy. Fuel trade Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers |
authorStr |
Stanisław Czapp |
ppnlink_with_tag_str_mv |
@@773@@(DE-627)1023271311 |
format |
electronic Article |
delete_txt_mv |
keep |
author_role |
aut aut aut |
collection |
DOAJ |
remote_str |
true |
callnumber-label |
HD9502-9502 |
illustrated |
Not Illustrated |
issn |
23003022 |
topic_title |
HD9502-9502.5 Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers residual current devices short-circuit currents back-up protection |
topic |
misc HD9502-9502.5 misc residual current devices misc short-circuit currents misc back-up protection misc Energy industries. Energy policy. Fuel trade |
topic_unstemmed |
misc HD9502-9502.5 misc residual current devices misc short-circuit currents misc back-up protection misc Energy industries. Energy policy. Fuel trade |
topic_browse |
misc HD9502-9502.5 misc residual current devices misc short-circuit currents misc back-up protection misc Energy industries. Energy policy. Fuel trade |
format_facet |
Elektronische Aufsätze Aufsätze Elektronische Ressource |
format_main_str_mv |
Text Zeitschrift/Artikel |
carriertype_str_mv |
cr |
hierarchy_parent_title |
Acta Energetica |
hierarchy_parent_id |
1023271311 |
hierarchy_top_title |
Acta Energetica |
isfreeaccess_txt |
true |
familylinks_str_mv |
(DE-627)1023271311 |
title |
Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers |
ctrlnum |
(DE-627)DOAJ002907399 (DE-599)DOAJba8e03432d4b469b866ab70d1f99c4a4 |
title_full |
Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers |
author_sort |
Stanisław Czapp |
journal |
Acta Energetica |
journalStr |
Acta Energetica |
callnumber-first-code |
H |
lang_code |
eng pol |
isOA_bool |
true |
recordtype |
marc |
publishDateSort |
2014 |
contenttype_str_mv |
txt |
container_start_page |
67 |
author_browse |
Stanisław Czapp Daniel Kowalak Kornel Borowski |
container_volume |
21 |
class |
HD9502-9502.5 |
format_se |
Elektronische Aufsätze |
author-letter |
Stanisław Czapp |
doi_str_mv |
10.12736/issn.2300-3022.2014406 |
author2-role |
verfasserin |
title_sort |
thermal and electrodynamic risk of residual current devices in the case of back-up protection by overcurrent circuit breakers |
callnumber |
HD9502-9502.5 |
title_auth |
Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers |
abstract |
Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed. |
abstractGer |
Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed. |
abstract_unstemmed |
Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed. |
collection_details |
GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_213 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_602 GBV_ILN_2014 GBV_ILN_4012 GBV_ILN_4037 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4249 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4335 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 |
container_issue |
4 |
title_short |
Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers |
url |
https://doi.org/10.12736/issn.2300-3022.2014406 https://doaj.org/article/ba8e03432d4b469b866ab70d1f99c4a4 http://actaenergetica.org/en/articles/acta-energetica-042014/thermal-and-electrodynamic-risk-of-residual-current-devices-in-the-case-of-back-up-protection-by-overcurrent-circuit-breakers/ https://doaj.org/toc/2300-3022 |
remote_bool |
true |
author2 |
Daniel Kowalak Kornel Borowski |
author2Str |
Daniel Kowalak Kornel Borowski |
ppnlink |
1023271311 |
callnumber-subject |
HD - Industries, Land Use, Labor |
mediatype_str_mv |
c |
isOA_txt |
true |
hochschulschrift_bool |
false |
doi_str |
10.12736/issn.2300-3022.2014406 |
callnumber-a |
HD9502-9502.5 |
up_date |
2024-07-03T14:48:34.751Z |
_version_ |
1803569714697338880 |
fullrecord_marcxml |
<?xml version="1.0" encoding="UTF-8"?><collection xmlns="http://www.loc.gov/MARC21/slim"><record><leader>01000caa a22002652 4500</leader><controlfield tag="001">DOAJ002907399</controlfield><controlfield tag="003">DE-627</controlfield><controlfield tag="005">20230309172438.0</controlfield><controlfield tag="007">cr uuu---uuuuu</controlfield><controlfield tag="008">230225s2014 xx |||||o 00| ||eng c</controlfield><datafield tag="024" ind1="7" ind2=" "><subfield code="a">10.12736/issn.2300-3022.2014406</subfield><subfield code="2">doi</subfield></datafield><datafield tag="035" ind1=" " ind2=" "><subfield code="a">(DE-627)DOAJ002907399</subfield></datafield><datafield tag="035" ind1=" " ind2=" "><subfield code="a">(DE-599)DOAJba8e03432d4b469b866ab70d1f99c4a4</subfield></datafield><datafield tag="040" ind1=" " ind2=" "><subfield code="a">DE-627</subfield><subfield code="b">ger</subfield><subfield code="c">DE-627</subfield><subfield code="e">rakwb</subfield></datafield><datafield tag="041" ind1=" " ind2=" "><subfield code="a">eng</subfield><subfield code="a">pol</subfield></datafield><datafield tag="050" ind1=" " ind2="0"><subfield code="a">HD9502-9502.5</subfield></datafield><datafield tag="100" ind1="0" ind2=" "><subfield code="a">Stanisław Czapp</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="245" ind1="1" ind2="0"><subfield code="a">Thermal and Electrodynamic Risk of Residual Current Devices in the Case of Back-Up Protection by Overcurrent Circuit Breakers</subfield></datafield><datafield tag="264" ind1=" " ind2="1"><subfield code="c">2014</subfield></datafield><datafield tag="336" ind1=" " ind2=" "><subfield code="a">Text</subfield><subfield code="b">txt</subfield><subfield code="2">rdacontent</subfield></datafield><datafield tag="337" ind1=" " ind2=" "><subfield code="a">Computermedien</subfield><subfield code="b">c</subfield><subfield code="2">rdamedia</subfield></datafield><datafield tag="338" ind1=" " ind2=" "><subfield code="a">Online-Ressource</subfield><subfield code="b">cr</subfield><subfield code="2">rdacarrier</subfield></datafield><datafield tag="520" ind1=" " ind2=" "><subfield code="a">Residual current operated circuit breakers without integral overcurrent protection should be back-up protected. As back-up protection devices, overcurrent circuit breakers are used. The maximum let-through energy and let-through current of the overcurrent devices were evaluated under laboratory conditions. The thermal and electrodynamic risk of residual current devices was analyzed.</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">residual current devices</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">short-circuit currents</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">back-up protection</subfield></datafield><datafield tag="653" ind1=" " ind2="0"><subfield code="a">Energy industries. Energy policy. Fuel trade</subfield></datafield><datafield tag="700" ind1="0" ind2=" "><subfield code="a">Daniel Kowalak</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="700" ind1="0" ind2=" "><subfield code="a">Kornel Borowski</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="773" ind1="0" ind2="8"><subfield code="i">In</subfield><subfield code="t">Acta Energetica</subfield><subfield code="d">ENERGA SA, 2016</subfield><subfield code="g">21(2014), 4, Seite 67-73</subfield><subfield code="w">(DE-627)1023271311</subfield><subfield code="x">23003022</subfield><subfield code="7">nnns</subfield></datafield><datafield tag="773" ind1="1" ind2="8"><subfield code="g">volume:21</subfield><subfield code="g">year:2014</subfield><subfield code="g">number:4</subfield><subfield code="g">pages:67-73</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">https://doi.org/10.12736/issn.2300-3022.2014406</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">https://doaj.org/article/ba8e03432d4b469b866ab70d1f99c4a4</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">http://actaenergetica.org/en/articles/acta-energetica-042014/thermal-and-electrodynamic-risk-of-residual-current-devices-in-the-case-of-back-up-protection-by-overcurrent-circuit-breakers/</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="2"><subfield code="u">https://doaj.org/toc/2300-3022</subfield><subfield code="y">Journal toc</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_USEFLAG_A</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">SYSFLAG_A</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_DOAJ</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_20</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_22</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_23</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_24</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_31</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_39</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_40</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_60</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_62</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_63</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_65</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_69</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_70</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_73</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_95</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_105</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_110</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_151</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_161</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_170</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_213</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_230</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_285</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_293</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_602</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2014</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4012</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4037</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4112</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4125</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4126</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4249</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4305</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4306</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4307</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4313</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4322</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4323</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4324</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4325</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4335</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4338</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4367</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4700</subfield></datafield><datafield tag="951" ind1=" " ind2=" "><subfield code="a">AR</subfield></datafield><datafield tag="952" ind1=" " ind2=" "><subfield code="d">21</subfield><subfield code="j">2014</subfield><subfield code="e">4</subfield><subfield code="h">67-73</subfield></datafield></record></collection>
|
score |
7.3984175 |