Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid
Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enha...
Ausführliche Beschreibung
Autor*in: |
Yashi Singh [verfasserIn] Bhim Singh [verfasserIn] Sukuma Mishra [verfasserIn] |
---|
Format: |
E-Artikel |
---|---|
Sprache: |
Englisch |
Erschienen: |
2022 |
---|
Schlagwörter: |
---|
Übergeordnetes Werk: |
In: IET Energy Systems Integration - Wiley, 2019, 4(2022), 3, Seite 351-367 |
---|---|
Übergeordnetes Werk: |
volume:4 ; year:2022 ; number:3 ; pages:351-367 |
Links: |
---|
DOI / URN: |
10.1049/esi2.12065 |
---|
Katalog-ID: |
DOAJ079336744 |
---|
LEADER | 01000naa a22002652 4500 | ||
---|---|---|---|
001 | DOAJ079336744 | ||
003 | DE-627 | ||
005 | 20230307014019.0 | ||
007 | cr uuu---uuuuu | ||
008 | 230307s2022 xx |||||o 00| ||eng c | ||
024 | 7 | |a 10.1049/esi2.12065 |2 doi | |
035 | |a (DE-627)DOAJ079336744 | ||
035 | |a (DE-599)DOAJ596620425eb04451a9de96168e49e59d | ||
040 | |a DE-627 |b ger |c DE-627 |e rakwb | ||
041 | |a eng | ||
050 | 0 | |a TK1001-1841 | |
050 | 0 | |a HD9502-9502.5 | |
100 | 0 | |a Yashi Singh |e verfasserin |4 aut | |
245 | 1 | 0 | |a Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid |
264 | 1 | |c 2022 | |
336 | |a Text |b txt |2 rdacontent | ||
337 | |a Computermedien |b c |2 rdamedia | ||
338 | |a Online-Ressource |b cr |2 rdacarrier | ||
520 | |a Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions. | ||
650 | 4 | |a dynamic loads | |
650 | 4 | |a grid synchronisation | |
650 | 4 | |a non‐linear loads | |
650 | 4 | |a solar energy | |
650 | 4 | |a voltage filtering and PQ | |
650 | 4 | |a wind energy | |
653 | 0 | |a Production of electric energy or power. Powerplants. Central stations | |
653 | 0 | |a Energy industries. Energy policy. Fuel trade | |
700 | 0 | |a Bhim Singh |e verfasserin |4 aut | |
700 | 0 | |a Sukuma Mishra |e verfasserin |4 aut | |
773 | 0 | 8 | |i In |t IET Energy Systems Integration |d Wiley, 2019 |g 4(2022), 3, Seite 351-367 |w (DE-627)1664846026 |x 25168401 |7 nnns |
773 | 1 | 8 | |g volume:4 |g year:2022 |g number:3 |g pages:351-367 |
856 | 4 | 0 | |u https://doi.org/10.1049/esi2.12065 |z kostenfrei |
856 | 4 | 0 | |u https://doaj.org/article/596620425eb04451a9de96168e49e59d |z kostenfrei |
856 | 4 | 0 | |u https://doi.org/10.1049/esi2.12065 |z kostenfrei |
856 | 4 | 2 | |u https://doaj.org/toc/2516-8401 |y Journal toc |z kostenfrei |
912 | |a GBV_USEFLAG_A | ||
912 | |a SYSFLAG_A | ||
912 | |a GBV_DOAJ | ||
912 | |a GBV_ILN_20 | ||
912 | |a GBV_ILN_22 | ||
912 | |a GBV_ILN_23 | ||
912 | |a GBV_ILN_24 | ||
912 | |a GBV_ILN_31 | ||
912 | |a GBV_ILN_39 | ||
912 | |a GBV_ILN_40 | ||
912 | |a GBV_ILN_60 | ||
912 | |a GBV_ILN_62 | ||
912 | |a GBV_ILN_63 | ||
912 | |a GBV_ILN_65 | ||
912 | |a GBV_ILN_69 | ||
912 | |a GBV_ILN_70 | ||
912 | |a GBV_ILN_73 | ||
912 | |a GBV_ILN_95 | ||
912 | |a GBV_ILN_105 | ||
912 | |a GBV_ILN_110 | ||
912 | |a GBV_ILN_151 | ||
912 | |a GBV_ILN_161 | ||
912 | |a GBV_ILN_170 | ||
912 | |a GBV_ILN_171 | ||
912 | |a GBV_ILN_213 | ||
912 | |a GBV_ILN_224 | ||
912 | |a GBV_ILN_230 | ||
912 | |a GBV_ILN_285 | ||
912 | |a GBV_ILN_293 | ||
912 | |a GBV_ILN_370 | ||
912 | |a GBV_ILN_602 | ||
912 | |a GBV_ILN_636 | ||
912 | |a GBV_ILN_2004 | ||
912 | |a GBV_ILN_2005 | ||
912 | |a GBV_ILN_2006 | ||
912 | |a GBV_ILN_2007 | ||
912 | |a GBV_ILN_2010 | ||
912 | |a GBV_ILN_2011 | ||
912 | |a GBV_ILN_2014 | ||
912 | |a GBV_ILN_2026 | ||
912 | |a GBV_ILN_2027 | ||
912 | |a GBV_ILN_2034 | ||
912 | |a GBV_ILN_2037 | ||
912 | |a GBV_ILN_2038 | ||
912 | |a GBV_ILN_2044 | ||
912 | |a GBV_ILN_2048 | ||
912 | |a GBV_ILN_2049 | ||
912 | |a GBV_ILN_2050 | ||
912 | |a GBV_ILN_2055 | ||
912 | |a GBV_ILN_2056 | ||
912 | |a GBV_ILN_2057 | ||
912 | |a GBV_ILN_2061 | ||
912 | |a GBV_ILN_2064 | ||
912 | |a GBV_ILN_2068 | ||
912 | |a GBV_ILN_2088 | ||
912 | |a GBV_ILN_2106 | ||
912 | |a GBV_ILN_2108 | ||
912 | |a GBV_ILN_2110 | ||
912 | |a GBV_ILN_2111 | ||
912 | |a GBV_ILN_2118 | ||
912 | |a GBV_ILN_2122 | ||
912 | |a GBV_ILN_2143 | ||
912 | |a GBV_ILN_2144 | ||
912 | |a GBV_ILN_2147 | ||
912 | |a GBV_ILN_2148 | ||
912 | |a GBV_ILN_2152 | ||
912 | |a GBV_ILN_2153 | ||
912 | |a GBV_ILN_2232 | ||
912 | |a GBV_ILN_2336 | ||
912 | |a GBV_ILN_2470 | ||
912 | |a GBV_ILN_2507 | ||
912 | |a GBV_ILN_2522 | ||
912 | |a GBV_ILN_4012 | ||
912 | |a GBV_ILN_4035 | ||
912 | |a GBV_ILN_4037 | ||
912 | |a GBV_ILN_4046 | ||
912 | |a GBV_ILN_4112 | ||
912 | |a GBV_ILN_4125 | ||
912 | |a GBV_ILN_4126 | ||
912 | |a GBV_ILN_4242 | ||
912 | |a GBV_ILN_4249 | ||
912 | |a GBV_ILN_4251 | ||
912 | |a GBV_ILN_4305 | ||
912 | |a GBV_ILN_4306 | ||
912 | |a GBV_ILN_4307 | ||
912 | |a GBV_ILN_4313 | ||
912 | |a GBV_ILN_4322 | ||
912 | |a GBV_ILN_4323 | ||
912 | |a GBV_ILN_4324 | ||
912 | |a GBV_ILN_4325 | ||
912 | |a GBV_ILN_4326 | ||
912 | |a GBV_ILN_4333 | ||
912 | |a GBV_ILN_4334 | ||
912 | |a GBV_ILN_4335 | ||
912 | |a GBV_ILN_4336 | ||
912 | |a GBV_ILN_4338 | ||
912 | |a GBV_ILN_4367 | ||
912 | |a GBV_ILN_4700 | ||
951 | |a AR | ||
952 | |d 4 |j 2022 |e 3 |h 351-367 |
author_variant |
y s ys b s bs s m sm |
---|---|
matchkey_str |
article:25168401:2022----::otoshmfridoapoootiadatrbsdirgicnieigy |
hierarchy_sort_str |
2022 |
callnumber-subject-code |
TK |
publishDate |
2022 |
allfields |
10.1049/esi2.12065 doi (DE-627)DOAJ079336744 (DE-599)DOAJ596620425eb04451a9de96168e49e59d DE-627 ger DE-627 rakwb eng TK1001-1841 HD9502-9502.5 Yashi Singh verfasserin aut Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid 2022 Text txt rdacontent Computermedien c rdamedia Online-Ressource cr rdacarrier Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions. dynamic loads grid synchronisation non‐linear loads solar energy voltage filtering and PQ wind energy Production of electric energy or power. Powerplants. Central stations Energy industries. Energy policy. Fuel trade Bhim Singh verfasserin aut Sukuma Mishra verfasserin aut In IET Energy Systems Integration Wiley, 2019 4(2022), 3, Seite 351-367 (DE-627)1664846026 25168401 nnns volume:4 year:2022 number:3 pages:351-367 https://doi.org/10.1049/esi2.12065 kostenfrei https://doaj.org/article/596620425eb04451a9de96168e49e59d kostenfrei https://doi.org/10.1049/esi2.12065 kostenfrei https://doaj.org/toc/2516-8401 Journal toc kostenfrei GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_171 GBV_ILN_213 GBV_ILN_224 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_370 GBV_ILN_602 GBV_ILN_636 GBV_ILN_2004 GBV_ILN_2005 GBV_ILN_2006 GBV_ILN_2007 GBV_ILN_2010 GBV_ILN_2011 GBV_ILN_2014 GBV_ILN_2026 GBV_ILN_2027 GBV_ILN_2034 GBV_ILN_2037 GBV_ILN_2038 GBV_ILN_2044 GBV_ILN_2048 GBV_ILN_2049 GBV_ILN_2050 GBV_ILN_2055 GBV_ILN_2056 GBV_ILN_2057 GBV_ILN_2061 GBV_ILN_2064 GBV_ILN_2068 GBV_ILN_2088 GBV_ILN_2106 GBV_ILN_2108 GBV_ILN_2110 GBV_ILN_2111 GBV_ILN_2118 GBV_ILN_2122 GBV_ILN_2143 GBV_ILN_2144 GBV_ILN_2147 GBV_ILN_2148 GBV_ILN_2152 GBV_ILN_2153 GBV_ILN_2232 GBV_ILN_2336 GBV_ILN_2470 GBV_ILN_2507 GBV_ILN_2522 GBV_ILN_4012 GBV_ILN_4035 GBV_ILN_4037 GBV_ILN_4046 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4242 GBV_ILN_4249 GBV_ILN_4251 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4326 GBV_ILN_4333 GBV_ILN_4334 GBV_ILN_4335 GBV_ILN_4336 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 AR 4 2022 3 351-367 |
spelling |
10.1049/esi2.12065 doi (DE-627)DOAJ079336744 (DE-599)DOAJ596620425eb04451a9de96168e49e59d DE-627 ger DE-627 rakwb eng TK1001-1841 HD9502-9502.5 Yashi Singh verfasserin aut Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid 2022 Text txt rdacontent Computermedien c rdamedia Online-Ressource cr rdacarrier Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions. dynamic loads grid synchronisation non‐linear loads solar energy voltage filtering and PQ wind energy Production of electric energy or power. Powerplants. Central stations Energy industries. Energy policy. Fuel trade Bhim Singh verfasserin aut Sukuma Mishra verfasserin aut In IET Energy Systems Integration Wiley, 2019 4(2022), 3, Seite 351-367 (DE-627)1664846026 25168401 nnns volume:4 year:2022 number:3 pages:351-367 https://doi.org/10.1049/esi2.12065 kostenfrei https://doaj.org/article/596620425eb04451a9de96168e49e59d kostenfrei https://doi.org/10.1049/esi2.12065 kostenfrei https://doaj.org/toc/2516-8401 Journal toc kostenfrei GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_171 GBV_ILN_213 GBV_ILN_224 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_370 GBV_ILN_602 GBV_ILN_636 GBV_ILN_2004 GBV_ILN_2005 GBV_ILN_2006 GBV_ILN_2007 GBV_ILN_2010 GBV_ILN_2011 GBV_ILN_2014 GBV_ILN_2026 GBV_ILN_2027 GBV_ILN_2034 GBV_ILN_2037 GBV_ILN_2038 GBV_ILN_2044 GBV_ILN_2048 GBV_ILN_2049 GBV_ILN_2050 GBV_ILN_2055 GBV_ILN_2056 GBV_ILN_2057 GBV_ILN_2061 GBV_ILN_2064 GBV_ILN_2068 GBV_ILN_2088 GBV_ILN_2106 GBV_ILN_2108 GBV_ILN_2110 GBV_ILN_2111 GBV_ILN_2118 GBV_ILN_2122 GBV_ILN_2143 GBV_ILN_2144 GBV_ILN_2147 GBV_ILN_2148 GBV_ILN_2152 GBV_ILN_2153 GBV_ILN_2232 GBV_ILN_2336 GBV_ILN_2470 GBV_ILN_2507 GBV_ILN_2522 GBV_ILN_4012 GBV_ILN_4035 GBV_ILN_4037 GBV_ILN_4046 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4242 GBV_ILN_4249 GBV_ILN_4251 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4326 GBV_ILN_4333 GBV_ILN_4334 GBV_ILN_4335 GBV_ILN_4336 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 AR 4 2022 3 351-367 |
allfields_unstemmed |
10.1049/esi2.12065 doi (DE-627)DOAJ079336744 (DE-599)DOAJ596620425eb04451a9de96168e49e59d DE-627 ger DE-627 rakwb eng TK1001-1841 HD9502-9502.5 Yashi Singh verfasserin aut Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid 2022 Text txt rdacontent Computermedien c rdamedia Online-Ressource cr rdacarrier Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions. dynamic loads grid synchronisation non‐linear loads solar energy voltage filtering and PQ wind energy Production of electric energy or power. Powerplants. Central stations Energy industries. Energy policy. Fuel trade Bhim Singh verfasserin aut Sukuma Mishra verfasserin aut In IET Energy Systems Integration Wiley, 2019 4(2022), 3, Seite 351-367 (DE-627)1664846026 25168401 nnns volume:4 year:2022 number:3 pages:351-367 https://doi.org/10.1049/esi2.12065 kostenfrei https://doaj.org/article/596620425eb04451a9de96168e49e59d kostenfrei https://doi.org/10.1049/esi2.12065 kostenfrei https://doaj.org/toc/2516-8401 Journal toc kostenfrei GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_171 GBV_ILN_213 GBV_ILN_224 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_370 GBV_ILN_602 GBV_ILN_636 GBV_ILN_2004 GBV_ILN_2005 GBV_ILN_2006 GBV_ILN_2007 GBV_ILN_2010 GBV_ILN_2011 GBV_ILN_2014 GBV_ILN_2026 GBV_ILN_2027 GBV_ILN_2034 GBV_ILN_2037 GBV_ILN_2038 GBV_ILN_2044 GBV_ILN_2048 GBV_ILN_2049 GBV_ILN_2050 GBV_ILN_2055 GBV_ILN_2056 GBV_ILN_2057 GBV_ILN_2061 GBV_ILN_2064 GBV_ILN_2068 GBV_ILN_2088 GBV_ILN_2106 GBV_ILN_2108 GBV_ILN_2110 GBV_ILN_2111 GBV_ILN_2118 GBV_ILN_2122 GBV_ILN_2143 GBV_ILN_2144 GBV_ILN_2147 GBV_ILN_2148 GBV_ILN_2152 GBV_ILN_2153 GBV_ILN_2232 GBV_ILN_2336 GBV_ILN_2470 GBV_ILN_2507 GBV_ILN_2522 GBV_ILN_4012 GBV_ILN_4035 GBV_ILN_4037 GBV_ILN_4046 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4242 GBV_ILN_4249 GBV_ILN_4251 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4326 GBV_ILN_4333 GBV_ILN_4334 GBV_ILN_4335 GBV_ILN_4336 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 AR 4 2022 3 351-367 |
allfieldsGer |
10.1049/esi2.12065 doi (DE-627)DOAJ079336744 (DE-599)DOAJ596620425eb04451a9de96168e49e59d DE-627 ger DE-627 rakwb eng TK1001-1841 HD9502-9502.5 Yashi Singh verfasserin aut Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid 2022 Text txt rdacontent Computermedien c rdamedia Online-Ressource cr rdacarrier Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions. dynamic loads grid synchronisation non‐linear loads solar energy voltage filtering and PQ wind energy Production of electric energy or power. Powerplants. Central stations Energy industries. Energy policy. Fuel trade Bhim Singh verfasserin aut Sukuma Mishra verfasserin aut In IET Energy Systems Integration Wiley, 2019 4(2022), 3, Seite 351-367 (DE-627)1664846026 25168401 nnns volume:4 year:2022 number:3 pages:351-367 https://doi.org/10.1049/esi2.12065 kostenfrei https://doaj.org/article/596620425eb04451a9de96168e49e59d kostenfrei https://doi.org/10.1049/esi2.12065 kostenfrei https://doaj.org/toc/2516-8401 Journal toc kostenfrei GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_171 GBV_ILN_213 GBV_ILN_224 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_370 GBV_ILN_602 GBV_ILN_636 GBV_ILN_2004 GBV_ILN_2005 GBV_ILN_2006 GBV_ILN_2007 GBV_ILN_2010 GBV_ILN_2011 GBV_ILN_2014 GBV_ILN_2026 GBV_ILN_2027 GBV_ILN_2034 GBV_ILN_2037 GBV_ILN_2038 GBV_ILN_2044 GBV_ILN_2048 GBV_ILN_2049 GBV_ILN_2050 GBV_ILN_2055 GBV_ILN_2056 GBV_ILN_2057 GBV_ILN_2061 GBV_ILN_2064 GBV_ILN_2068 GBV_ILN_2088 GBV_ILN_2106 GBV_ILN_2108 GBV_ILN_2110 GBV_ILN_2111 GBV_ILN_2118 GBV_ILN_2122 GBV_ILN_2143 GBV_ILN_2144 GBV_ILN_2147 GBV_ILN_2148 GBV_ILN_2152 GBV_ILN_2153 GBV_ILN_2232 GBV_ILN_2336 GBV_ILN_2470 GBV_ILN_2507 GBV_ILN_2522 GBV_ILN_4012 GBV_ILN_4035 GBV_ILN_4037 GBV_ILN_4046 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4242 GBV_ILN_4249 GBV_ILN_4251 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4326 GBV_ILN_4333 GBV_ILN_4334 GBV_ILN_4335 GBV_ILN_4336 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 AR 4 2022 3 351-367 |
allfieldsSound |
10.1049/esi2.12065 doi (DE-627)DOAJ079336744 (DE-599)DOAJ596620425eb04451a9de96168e49e59d DE-627 ger DE-627 rakwb eng TK1001-1841 HD9502-9502.5 Yashi Singh verfasserin aut Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid 2022 Text txt rdacontent Computermedien c rdamedia Online-Ressource cr rdacarrier Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions. dynamic loads grid synchronisation non‐linear loads solar energy voltage filtering and PQ wind energy Production of electric energy or power. Powerplants. Central stations Energy industries. Energy policy. Fuel trade Bhim Singh verfasserin aut Sukuma Mishra verfasserin aut In IET Energy Systems Integration Wiley, 2019 4(2022), 3, Seite 351-367 (DE-627)1664846026 25168401 nnns volume:4 year:2022 number:3 pages:351-367 https://doi.org/10.1049/esi2.12065 kostenfrei https://doaj.org/article/596620425eb04451a9de96168e49e59d kostenfrei https://doi.org/10.1049/esi2.12065 kostenfrei https://doaj.org/toc/2516-8401 Journal toc kostenfrei GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_171 GBV_ILN_213 GBV_ILN_224 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_370 GBV_ILN_602 GBV_ILN_636 GBV_ILN_2004 GBV_ILN_2005 GBV_ILN_2006 GBV_ILN_2007 GBV_ILN_2010 GBV_ILN_2011 GBV_ILN_2014 GBV_ILN_2026 GBV_ILN_2027 GBV_ILN_2034 GBV_ILN_2037 GBV_ILN_2038 GBV_ILN_2044 GBV_ILN_2048 GBV_ILN_2049 GBV_ILN_2050 GBV_ILN_2055 GBV_ILN_2056 GBV_ILN_2057 GBV_ILN_2061 GBV_ILN_2064 GBV_ILN_2068 GBV_ILN_2088 GBV_ILN_2106 GBV_ILN_2108 GBV_ILN_2110 GBV_ILN_2111 GBV_ILN_2118 GBV_ILN_2122 GBV_ILN_2143 GBV_ILN_2144 GBV_ILN_2147 GBV_ILN_2148 GBV_ILN_2152 GBV_ILN_2153 GBV_ILN_2232 GBV_ILN_2336 GBV_ILN_2470 GBV_ILN_2507 GBV_ILN_2522 GBV_ILN_4012 GBV_ILN_4035 GBV_ILN_4037 GBV_ILN_4046 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4242 GBV_ILN_4249 GBV_ILN_4251 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4326 GBV_ILN_4333 GBV_ILN_4334 GBV_ILN_4335 GBV_ILN_4336 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 AR 4 2022 3 351-367 |
language |
English |
source |
In IET Energy Systems Integration 4(2022), 3, Seite 351-367 volume:4 year:2022 number:3 pages:351-367 |
sourceStr |
In IET Energy Systems Integration 4(2022), 3, Seite 351-367 volume:4 year:2022 number:3 pages:351-367 |
format_phy_str_mv |
Article |
institution |
findex.gbv.de |
topic_facet |
dynamic loads grid synchronisation non‐linear loads solar energy voltage filtering and PQ wind energy Production of electric energy or power. Powerplants. Central stations Energy industries. Energy policy. Fuel trade |
isfreeaccess_bool |
true |
container_title |
IET Energy Systems Integration |
authorswithroles_txt_mv |
Yashi Singh @@aut@@ Bhim Singh @@aut@@ Sukuma Mishra @@aut@@ |
publishDateDaySort_date |
2022-01-01T00:00:00Z |
hierarchy_top_id |
1664846026 |
id |
DOAJ079336744 |
language_de |
englisch |
fullrecord |
<?xml version="1.0" encoding="UTF-8"?><collection xmlns="http://www.loc.gov/MARC21/slim"><record><leader>01000naa a22002652 4500</leader><controlfield tag="001">DOAJ079336744</controlfield><controlfield tag="003">DE-627</controlfield><controlfield tag="005">20230307014019.0</controlfield><controlfield tag="007">cr uuu---uuuuu</controlfield><controlfield tag="008">230307s2022 xx |||||o 00| ||eng c</controlfield><datafield tag="024" ind1="7" ind2=" "><subfield code="a">10.1049/esi2.12065</subfield><subfield code="2">doi</subfield></datafield><datafield tag="035" ind1=" " ind2=" "><subfield code="a">(DE-627)DOAJ079336744</subfield></datafield><datafield tag="035" ind1=" " ind2=" "><subfield code="a">(DE-599)DOAJ596620425eb04451a9de96168e49e59d</subfield></datafield><datafield tag="040" ind1=" " ind2=" "><subfield code="a">DE-627</subfield><subfield code="b">ger</subfield><subfield code="c">DE-627</subfield><subfield code="e">rakwb</subfield></datafield><datafield tag="041" ind1=" " ind2=" "><subfield code="a">eng</subfield></datafield><datafield tag="050" ind1=" " ind2="0"><subfield code="a">TK1001-1841</subfield></datafield><datafield tag="050" ind1=" " ind2="0"><subfield code="a">HD9502-9502.5</subfield></datafield><datafield tag="100" ind1="0" ind2=" "><subfield code="a">Yashi Singh</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="245" ind1="1" ind2="0"><subfield code="a">Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid</subfield></datafield><datafield tag="264" ind1=" " ind2="1"><subfield code="c">2022</subfield></datafield><datafield tag="336" ind1=" " ind2=" "><subfield code="a">Text</subfield><subfield code="b">txt</subfield><subfield code="2">rdacontent</subfield></datafield><datafield tag="337" ind1=" " ind2=" "><subfield code="a">Computermedien</subfield><subfield code="b">c</subfield><subfield code="2">rdamedia</subfield></datafield><datafield tag="338" ind1=" " ind2=" "><subfield code="a">Online-Ressource</subfield><subfield code="b">cr</subfield><subfield code="2">rdacarrier</subfield></datafield><datafield tag="520" ind1=" " ind2=" "><subfield code="a">Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions.</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">dynamic loads</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">grid synchronisation</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">non‐linear loads</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">solar energy</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">voltage filtering and PQ</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">wind energy</subfield></datafield><datafield tag="653" ind1=" " ind2="0"><subfield code="a">Production of electric energy or power. Powerplants. Central stations</subfield></datafield><datafield tag="653" ind1=" " ind2="0"><subfield code="a">Energy industries. Energy policy. Fuel trade</subfield></datafield><datafield tag="700" ind1="0" ind2=" "><subfield code="a">Bhim Singh</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="700" ind1="0" ind2=" "><subfield code="a">Sukuma Mishra</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="773" ind1="0" ind2="8"><subfield code="i">In</subfield><subfield code="t">IET Energy Systems Integration</subfield><subfield code="d">Wiley, 2019</subfield><subfield code="g">4(2022), 3, Seite 351-367</subfield><subfield code="w">(DE-627)1664846026</subfield><subfield code="x">25168401</subfield><subfield code="7">nnns</subfield></datafield><datafield tag="773" ind1="1" ind2="8"><subfield code="g">volume:4</subfield><subfield code="g">year:2022</subfield><subfield code="g">number:3</subfield><subfield code="g">pages:351-367</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">https://doi.org/10.1049/esi2.12065</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">https://doaj.org/article/596620425eb04451a9de96168e49e59d</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">https://doi.org/10.1049/esi2.12065</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="2"><subfield code="u">https://doaj.org/toc/2516-8401</subfield><subfield code="y">Journal toc</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_USEFLAG_A</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">SYSFLAG_A</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_DOAJ</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_20</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_22</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_23</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_24</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_31</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_39</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_40</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_60</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_62</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_63</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_65</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_69</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_70</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_73</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_95</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_105</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_110</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_151</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_161</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_170</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_171</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_213</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_224</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_230</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_285</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_293</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_370</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_602</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_636</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2004</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2005</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2006</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2007</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2010</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2011</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2014</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2026</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2027</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2034</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2037</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2038</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2044</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2048</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2049</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2050</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2055</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2056</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2057</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2061</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2064</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2068</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2088</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2106</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2108</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2110</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2111</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2118</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2122</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2143</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2144</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2147</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2148</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2152</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2153</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2232</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2336</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2470</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2507</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2522</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4012</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4035</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4037</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4046</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4112</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4125</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4126</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4242</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4249</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4251</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4305</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4306</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4307</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4313</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4322</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4323</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4324</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4325</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4326</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4333</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4334</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4335</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4336</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4338</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4367</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4700</subfield></datafield><datafield tag="951" ind1=" " ind2=" "><subfield code="a">AR</subfield></datafield><datafield tag="952" ind1=" " ind2=" "><subfield code="d">4</subfield><subfield code="j">2022</subfield><subfield code="e">3</subfield><subfield code="h">351-367</subfield></datafield></record></collection>
|
callnumber-first |
T - Technology |
author |
Yashi Singh |
spellingShingle |
Yashi Singh misc TK1001-1841 misc HD9502-9502.5 misc dynamic loads misc grid synchronisation misc non‐linear loads misc solar energy misc voltage filtering and PQ misc wind energy misc Production of electric energy or power. Powerplants. Central stations misc Energy industries. Energy policy. Fuel trade Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid |
authorStr |
Yashi Singh |
ppnlink_with_tag_str_mv |
@@773@@(DE-627)1664846026 |
format |
electronic Article |
delete_txt_mv |
keep |
author_role |
aut aut aut |
collection |
DOAJ |
remote_str |
true |
callnumber-label |
TK1001-1841 |
illustrated |
Not Illustrated |
issn |
25168401 |
topic_title |
TK1001-1841 HD9502-9502.5 Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid dynamic loads grid synchronisation non‐linear loads solar energy voltage filtering and PQ wind energy |
topic |
misc TK1001-1841 misc HD9502-9502.5 misc dynamic loads misc grid synchronisation misc non‐linear loads misc solar energy misc voltage filtering and PQ misc wind energy misc Production of electric energy or power. Powerplants. Central stations misc Energy industries. Energy policy. Fuel trade |
topic_unstemmed |
misc TK1001-1841 misc HD9502-9502.5 misc dynamic loads misc grid synchronisation misc non‐linear loads misc solar energy misc voltage filtering and PQ misc wind energy misc Production of electric energy or power. Powerplants. Central stations misc Energy industries. Energy policy. Fuel trade |
topic_browse |
misc TK1001-1841 misc HD9502-9502.5 misc dynamic loads misc grid synchronisation misc non‐linear loads misc solar energy misc voltage filtering and PQ misc wind energy misc Production of electric energy or power. Powerplants. Central stations misc Energy industries. Energy policy. Fuel trade |
format_facet |
Elektronische Aufsätze Aufsätze Elektronische Ressource |
format_main_str_mv |
Text Zeitschrift/Artikel |
carriertype_str_mv |
cr |
hierarchy_parent_title |
IET Energy Systems Integration |
hierarchy_parent_id |
1664846026 |
hierarchy_top_title |
IET Energy Systems Integration |
isfreeaccess_txt |
true |
familylinks_str_mv |
(DE-627)1664846026 |
title |
Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid |
ctrlnum |
(DE-627)DOAJ079336744 (DE-599)DOAJ596620425eb04451a9de96168e49e59d |
title_full |
Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid |
author_sort |
Yashi Singh |
journal |
IET Energy Systems Integration |
journalStr |
IET Energy Systems Integration |
callnumber-first-code |
T |
lang_code |
eng |
isOA_bool |
true |
recordtype |
marc |
publishDateSort |
2022 |
contenttype_str_mv |
txt |
container_start_page |
351 |
author_browse |
Yashi Singh Bhim Singh Sukuma Mishra |
container_volume |
4 |
class |
TK1001-1841 HD9502-9502.5 |
format_se |
Elektronische Aufsätze |
author-letter |
Yashi Singh |
doi_str_mv |
10.1049/esi2.12065 |
author2-role |
verfasserin |
title_sort |
control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid |
callnumber |
TK1001-1841 |
title_auth |
Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid |
abstract |
Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions. |
abstractGer |
Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions. |
abstract_unstemmed |
Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions. |
collection_details |
GBV_USEFLAG_A SYSFLAG_A GBV_DOAJ GBV_ILN_20 GBV_ILN_22 GBV_ILN_23 GBV_ILN_24 GBV_ILN_31 GBV_ILN_39 GBV_ILN_40 GBV_ILN_60 GBV_ILN_62 GBV_ILN_63 GBV_ILN_65 GBV_ILN_69 GBV_ILN_70 GBV_ILN_73 GBV_ILN_95 GBV_ILN_105 GBV_ILN_110 GBV_ILN_151 GBV_ILN_161 GBV_ILN_170 GBV_ILN_171 GBV_ILN_213 GBV_ILN_224 GBV_ILN_230 GBV_ILN_285 GBV_ILN_293 GBV_ILN_370 GBV_ILN_602 GBV_ILN_636 GBV_ILN_2004 GBV_ILN_2005 GBV_ILN_2006 GBV_ILN_2007 GBV_ILN_2010 GBV_ILN_2011 GBV_ILN_2014 GBV_ILN_2026 GBV_ILN_2027 GBV_ILN_2034 GBV_ILN_2037 GBV_ILN_2038 GBV_ILN_2044 GBV_ILN_2048 GBV_ILN_2049 GBV_ILN_2050 GBV_ILN_2055 GBV_ILN_2056 GBV_ILN_2057 GBV_ILN_2061 GBV_ILN_2064 GBV_ILN_2068 GBV_ILN_2088 GBV_ILN_2106 GBV_ILN_2108 GBV_ILN_2110 GBV_ILN_2111 GBV_ILN_2118 GBV_ILN_2122 GBV_ILN_2143 GBV_ILN_2144 GBV_ILN_2147 GBV_ILN_2148 GBV_ILN_2152 GBV_ILN_2153 GBV_ILN_2232 GBV_ILN_2336 GBV_ILN_2470 GBV_ILN_2507 GBV_ILN_2522 GBV_ILN_4012 GBV_ILN_4035 GBV_ILN_4037 GBV_ILN_4046 GBV_ILN_4112 GBV_ILN_4125 GBV_ILN_4126 GBV_ILN_4242 GBV_ILN_4249 GBV_ILN_4251 GBV_ILN_4305 GBV_ILN_4306 GBV_ILN_4307 GBV_ILN_4313 GBV_ILN_4322 GBV_ILN_4323 GBV_ILN_4324 GBV_ILN_4325 GBV_ILN_4326 GBV_ILN_4333 GBV_ILN_4334 GBV_ILN_4335 GBV_ILN_4336 GBV_ILN_4338 GBV_ILN_4367 GBV_ILN_4700 |
container_issue |
3 |
title_short |
Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid |
url |
https://doi.org/10.1049/esi2.12065 https://doaj.org/article/596620425eb04451a9de96168e49e59d https://doaj.org/toc/2516-8401 |
remote_bool |
true |
author2 |
Bhim Singh Sukuma Mishra |
author2Str |
Bhim Singh Sukuma Mishra |
ppnlink |
1664846026 |
callnumber-subject |
TK - Electrical and Nuclear Engineering |
mediatype_str_mv |
c |
isOA_txt |
true |
hochschulschrift_bool |
false |
doi_str |
10.1049/esi2.12065 |
callnumber-a |
TK1001-1841 |
up_date |
2024-07-03T22:57:54.604Z |
_version_ |
1803600500730363904 |
fullrecord_marcxml |
<?xml version="1.0" encoding="UTF-8"?><collection xmlns="http://www.loc.gov/MARC21/slim"><record><leader>01000naa a22002652 4500</leader><controlfield tag="001">DOAJ079336744</controlfield><controlfield tag="003">DE-627</controlfield><controlfield tag="005">20230307014019.0</controlfield><controlfield tag="007">cr uuu---uuuuu</controlfield><controlfield tag="008">230307s2022 xx |||||o 00| ||eng c</controlfield><datafield tag="024" ind1="7" ind2=" "><subfield code="a">10.1049/esi2.12065</subfield><subfield code="2">doi</subfield></datafield><datafield tag="035" ind1=" " ind2=" "><subfield code="a">(DE-627)DOAJ079336744</subfield></datafield><datafield tag="035" ind1=" " ind2=" "><subfield code="a">(DE-599)DOAJ596620425eb04451a9de96168e49e59d</subfield></datafield><datafield tag="040" ind1=" " ind2=" "><subfield code="a">DE-627</subfield><subfield code="b">ger</subfield><subfield code="c">DE-627</subfield><subfield code="e">rakwb</subfield></datafield><datafield tag="041" ind1=" " ind2=" "><subfield code="a">eng</subfield></datafield><datafield tag="050" ind1=" " ind2="0"><subfield code="a">TK1001-1841</subfield></datafield><datafield tag="050" ind1=" " ind2="0"><subfield code="a">HD9502-9502.5</subfield></datafield><datafield tag="100" ind1="0" ind2=" "><subfield code="a">Yashi Singh</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="245" ind1="1" ind2="0"><subfield code="a">Control scheme for wind–solar photovoltaic and battery‐based microgrid considering dynamic loads and distorted grid</subfield></datafield><datafield tag="264" ind1=" " ind2="1"><subfield code="c">2022</subfield></datafield><datafield tag="336" ind1=" " ind2=" "><subfield code="a">Text</subfield><subfield code="b">txt</subfield><subfield code="2">rdacontent</subfield></datafield><datafield tag="337" ind1=" " ind2=" "><subfield code="a">Computermedien</subfield><subfield code="b">c</subfield><subfield code="2">rdamedia</subfield></datafield><datafield tag="338" ind1=" " ind2=" "><subfield code="a">Online-Ressource</subfield><subfield code="b">cr</subfield><subfield code="2">rdacarrier</subfield></datafield><datafield tag="520" ind1=" " ind2=" "><subfield code="a">Abstract A concern regarding the deterioration in power quality (PQ) has escalated with the high level of integration of renewable energy sources to the utility, primarily in the scenario of a weak distribution grid. This paper presents a modified complex variable filter (MCVF)‐based control to enhance the power quality performance of wind–solar photovoltaic (PV) and battery‐based microgrid under the weak grid and dynamic load conditions. An MCVF attenuates the harmonics and DC bias infected voltage and current and extracts the fundamental components from distorted current and voltage. The control scheme for the voltage source converter (VSC) is presented to meet the active power demand of load/grid and attenuates harmonics to control the power quality issues at the point of common coupling. To achieve the round, the clock operation of the microgrid, a battery is interfaced to support the local loads under off‐grid mode. Therefore, the presented VSC controller supplies the continuous power to the local loads and maintains the total harmonic distortion value of grid current within the PQ Standard IEEE‐519‐2014. The simulated and test results are presented to validate the VSC controller in different operating conditions.</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">dynamic loads</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">grid synchronisation</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">non‐linear loads</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">solar energy</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">voltage filtering and PQ</subfield></datafield><datafield tag="650" ind1=" " ind2="4"><subfield code="a">wind energy</subfield></datafield><datafield tag="653" ind1=" " ind2="0"><subfield code="a">Production of electric energy or power. Powerplants. Central stations</subfield></datafield><datafield tag="653" ind1=" " ind2="0"><subfield code="a">Energy industries. Energy policy. Fuel trade</subfield></datafield><datafield tag="700" ind1="0" ind2=" "><subfield code="a">Bhim Singh</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="700" ind1="0" ind2=" "><subfield code="a">Sukuma Mishra</subfield><subfield code="e">verfasserin</subfield><subfield code="4">aut</subfield></datafield><datafield tag="773" ind1="0" ind2="8"><subfield code="i">In</subfield><subfield code="t">IET Energy Systems Integration</subfield><subfield code="d">Wiley, 2019</subfield><subfield code="g">4(2022), 3, Seite 351-367</subfield><subfield code="w">(DE-627)1664846026</subfield><subfield code="x">25168401</subfield><subfield code="7">nnns</subfield></datafield><datafield tag="773" ind1="1" ind2="8"><subfield code="g">volume:4</subfield><subfield code="g">year:2022</subfield><subfield code="g">number:3</subfield><subfield code="g">pages:351-367</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">https://doi.org/10.1049/esi2.12065</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">https://doaj.org/article/596620425eb04451a9de96168e49e59d</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="0"><subfield code="u">https://doi.org/10.1049/esi2.12065</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="856" ind1="4" ind2="2"><subfield code="u">https://doaj.org/toc/2516-8401</subfield><subfield code="y">Journal toc</subfield><subfield code="z">kostenfrei</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_USEFLAG_A</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">SYSFLAG_A</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_DOAJ</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_20</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_22</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_23</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_24</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_31</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_39</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_40</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_60</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_62</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_63</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_65</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_69</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_70</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_73</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_95</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_105</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_110</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_151</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_161</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_170</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_171</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_213</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_224</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_230</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_285</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_293</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_370</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_602</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_636</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2004</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2005</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2006</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2007</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2010</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2011</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2014</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2026</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2027</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2034</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2037</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2038</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2044</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2048</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2049</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2050</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2055</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2056</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2057</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2061</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2064</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2068</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2088</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2106</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2108</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2110</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2111</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2118</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2122</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2143</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2144</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2147</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2148</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2152</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2153</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2232</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2336</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2470</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2507</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_2522</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4012</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4035</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4037</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4046</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4112</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4125</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4126</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4242</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4249</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4251</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4305</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4306</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4307</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4313</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4322</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4323</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4324</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4325</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4326</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4333</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4334</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4335</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4336</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4338</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4367</subfield></datafield><datafield tag="912" ind1=" " ind2=" "><subfield code="a">GBV_ILN_4700</subfield></datafield><datafield tag="951" ind1=" " ind2=" "><subfield code="a">AR</subfield></datafield><datafield tag="952" ind1=" " ind2=" "><subfield code="d">4</subfield><subfield code="j">2022</subfield><subfield code="e">3</subfield><subfield code="h">351-367</subfield></datafield></record></collection>
|
score |
7.3990107 |